When a 100GBASE‑SR4 link reports a failure, the most reliable first step is to verify the MPO polarity before moving to more invasive checks. A typical polarity‑check order is:

1. Confirm that the host transceiver is a native 100G‑SR4 (four‑lane) module, not a 4×25G breakout. The host should report a 4‑lane configuration in its DDM/DOM data; a breakout will show four separate 25G lanes.
2. Identify the MPO connector type. SR4 uses MPO‑Type B (also called “MPO‑B”) with a defined pin‑out. Verify that both ends use the same type; a mismatch (Type A vs. Type B) will invert TX/RX lanes.
3. Use a polarity‑test cable or a loop‑back MPO patch cord to inject a known optical signal on each lane. Measure per‑lane Rx power via the DOM; typical Rx power for SR4 is –8 dBm to –2 dBm at 100 m. A lane reading outside this range often indicates a polarity error.
4. If the lane powers are inverted (e.g., lane 1 Rx shows the power of lane 4 Tx), swap the MPO connectors or re‑terminate the MPO cable with the correct polarity.
5. After correcting polarity, re‑read the DDM values. Ensure that the module’s Tx bias and temperature are within spec; abnormal bias can also cause a link‑down state.

This sequence isolates the most common polarity‑related failure mode while keeping the optical path untouched. If power levels remain abnormal after confirming correct polarity, the next step is to check for fiber‑optic loss or a defective MPO cable.