For a failing SR4 link, start by confirming the intended mode: native 100G over four lanes, or a 4x25G breakout. The polarity check differs. Native SR4 needs a Type A, B, or C MPO cord matched to both endpoints and the panel; a wrong crossover can put lanes in a permutation that some hosts tolerate and others do not. Breakout usually needs a fanout assembly whose lane mapping matches the switch-side breakout configuration, not just a generic MPO trunk. After polarity, read per-lane DOM Rx power if the modules expose it. A lane showing -10 dBm while neighbors sit near -2 dBm points to one bad fiber or a dirty connector, not a module-wide fault. Swap the MPO jumper first, then clean both MPO and LC ends with a certified cleaner. Typical SR4 budget over OM3 is around 30 m at 100G and shorter for breakout runs; OM4 roughly doubles it. What per-lane Rx spread does your switch show on the failing link?