When a 100G SR4 link works in both directions but only a subset of the four lanes carries traffic, the first step is to verify the physical configuration before chasing software mapping. Start by confirming whether the installed SR4 module is a native 100G SR4 (four‑lane, 25 Gbps each) or a 4×25G breakout (four independent 25G SFP28 ports on a QSFP28 chassis). The part number and the module’s EEPROM data (look for "Form Factor" and "Lane Count") will indicate the mode; a breakout will expose four separate transceiver IDs in the DOM.
If the module is native, the MPO connector must be wired with Type‑B polarity (pins 1‑2‑3‑4 on one side to pins 4‑3‑2‑1 on the other). A polarity swap will cause two lanes to see reverse polarity, which often manifests as loss of traffic while the optical power appears nominal. Check the MPO keying and, if possible, verify the pin‑to‑pin mapping with a continuity tester or a known‑good MPO cable.
Next, pull the per‑lane DOM statistics (Rx power, Tx power, temperature). Typical Rx power for a 100G SR4 link is around –6 dBm ± 3 dB per lane. If one or more lanes show power outside this window, the issue is likely a fiber defect, connector contamination, or a faulty MPO ferrule. Clean the MPO ends with a lint‑free wipe and isopropyl alcohol, then re‑measure.
Only after confirming correct polarity and acceptable per‑lane power should you examine the switch or NIC lane mapping tables for any static or dynamic lane assignment mismatches.
What tools or scripts have you found most reliable for extracting and correlating per‑lane DOM data on multi‑lane 100G modules?
If the module is native, the MPO connector must be wired with Type‑B polarity (pins 1‑2‑3‑4 on one side to pins 4‑3‑2‑1 on the other). A polarity swap will cause two lanes to see reverse polarity, which often manifests as loss of traffic while the optical power appears nominal. Check the MPO keying and, if possible, verify the pin‑to‑pin mapping with a continuity tester or a known‑good MPO cable.
Next, pull the per‑lane DOM statistics (Rx power, Tx power, temperature). Typical Rx power for a 100G SR4 link is around –6 dBm ± 3 dB per lane. If one or more lanes show power outside this window, the issue is likely a fiber defect, connector contamination, or a faulty MPO ferrule. Clean the MPO ends with a lint‑free wipe and isopropyl alcohol, then re‑measure.
Only after confirming correct polarity and acceptable per‑lane power should you examine the switch or NIC lane mapping tables for any static or dynamic lane assignment mismatches.
What tools or scripts have you found most reliable for extracting and correlating per‑lane DOM data on multi‑lane 100G modules?